MODBUS protocol for Danfoss ECL Comfort 110

Physical

The device has a RS-485 transceiver (SN75LBC184P), for which connections are brought out on the display/buttons daughterboard.

Front view of the pinout:

1 2 3 4
GND D- / B D+ / A +5V DC ?? mA

The connector is Wieland DST85 / 4 (Art. No. 25.002.0453.0 and 25.003.0453.0). Connectors that ship within Europe can be bought from user aviborg on eBay. The best image of the connector from Danfoss can be seen from their Danfoss Link installation video.

The main microcontroller is Renesas R5F21258SN.

There are also six 0.1" headers on the main PCB that are probably used for servicing the device (flashing firmwares, debugging, ...). It uses 3.3V logic.

2 4 6
TXD VCC GND
RXD nRESET MODE
1 3 5

Serial settings

  • Baud rate: 19200
  • Data bits: 8
  • Parity: Even
  • Stop bits: 1

Communication

Communication is done using MODBUS RTU. The following values have been gathered from application 116/130, software version 1.06

Read/Write MODBUS register (PNU) Line Notes
Monday Start1 RW 1109 N/A Format: XXYY decimal where XX = 00..23 and YY = 00 or 30, XXYY = 2400 is also accepted. Value means time XX:YY.
Monday Stop1 RW 1110 N/A
Monday Start2 RW 1111 N/A
Monday Stop2 RW 1112 N/A
Tuesday Start1 RW 1119 N/A
Tuesday Stop1 RW 1120 N/A
Tuesday Start2 RW 1121 N/A
Tuesday Stop2 RW 1122 N/A
Wednesday Start1 RW 1129 N/A
Wednesday Stop1 RW 1130 N/A
Wednesday Start2 RW 1131 N/A
Wednesday Stop2 RW 1132 N/A
Thursday Start1 RW 1139 N/A
Thursday Stop1 RW 1140 N/A
Thursday Start2 RW 1141 N/A
Thursday Stop2 RW 1142 N/A
Friday Start1 RW 1149 N/A
Friday Stop1 RW 1150 N/A
Friday Start2 RW 1151 N/A
Friday Stop2 RW 1152 N/A
Saturday Start1 RW 1159 N/A
Saturday Stop1 RW 1160 N/A
Saturday Start2 RW 1161 N/A
Saturday Stop2 RW 1162 N/A
Sunday Start1 RW 1169 N/A
Sunday Stop1 RW 1170 N/A
Sunday Start2 RW 1171 N/A
Sunday Stop2 RW 1172 N/A
??? R? 2002 N/A
MOD address (MODBUS address) R/W 2007 8320 Valid values: 0...247
??? R? 2010 N/A
??? R? 2014 N/A
Language RW 2027 8315 0 = English
1 = Swedish
2 = Danish
3 = Finnish
4 = German
5 = Estonian
6 = Lithuanian
7 = Latvian
8 = Polish
??? R? 2102 N/A
??? R? 2103 N/A
??? R? 2104 N/A
??? R? 2105 N/A
??? R? 2106 N/A
??? R? 2107 N/A
??? R? 2108 N/A
??? R? 2109 N/A
??? R? 2110 N/A
R? 4001 N/A Pump on/off
R? 4100 N/A Valve open?
R? 4101 N/A Valve shut?
R? 4200 N/A Desired Mode (AUTO/COMFORT/SETBACK/STANDBY)
R? 4210 N/A Actual mode ?
??? R? 4614 N/A
ECA address (choice of room panel / remote control) RW 11009 7010 Application 130 only.
0 = OFF
1 = A
2 = B
Auto-reduct (setback temp. dependent on outdoor temp.) RW 11010 5011 Application 130 only. TODO: FORMAT
Boost RW 11011 5012 Application 130 only. TODO: FORMAT
Ramp (reference ramping) RW 11012 5013 Application 130 only. TODO: FORMAT
Optimizer (optimizing time constant) RW 11013 5014 Application 130 only. TODO: FORMAT
Intgr. time (time constant for room temp.) RW 11014 3015 Application 130 only. TODO: FORMAT
Based on (optimization based on room / outdoor temp.) RW 11019 5020 Application 130 only. TODO: FORMAT
Total stop RW 11020 5021 Application 130 only. TODO: FORMAT
P1 exercise (pump exercise) RW 11021 7022 TODO: FORMAT
M1 exercise (valve exercise) RW 11022 7023 TODO: FORMAT
Actuator (gear motor / thermo actuator) RW 11023 7024 Application 130 only. TODO: FORMAT
Limit (return temp. limitation) RW 11029 4030 TODO: FORMAT
Gain - max. (return temp. limitation - max. influence) RW 11034 4035 TODO: FORMAT
Gain - min. (return temp. limitation - min. influence) RW 11035 4036 TODO: FORMAT
Intgr. time (time constant for return temp. limitation) RW 11036 4037 TODO: FORMAT
DHW prior. (closed valve / normal operation) RW 11051 7052 Application 130 only. TODO: FORMAT
P1 frost T (frost protection) RW 11076 7077 TODO: FORMAT
P1 heat T (heat demand) RW 11077 7078 TODO: FORMAT
Priority (priority for return temp. limitation) RW 11084 4085 Application 130 only. TODO: FORMAT
Standby T (standby temperature) RW 11092 7093 TODO: FORMAT
??? R? 11099 N/A Application 130 only. Accumulated Outside Temperature?
Ext. (external override) RW 11140 7141 TODO: FORMAT
Knee point RW 11161 7162 TODO: FORMAT
??? R? 11173 N/A Application 116 only.
Motor prot. (motor protection) RW 11173 6174 Application 130 only. TODO: FORMAT
Slope RW 11174 2175 Application 130 only. TODO: FORMAT
Displace (parallel displacement) RW 11175 2176 Application 130 only. TODO: FORMAT
Temp. min. (flow temp. limit, min.) RW 11176 2177 TODO: FORMAT
Temp. max. (flow temp. limit, max.) RW 11177 2178 TODO: FORMAT
Cut-out (limit for heating cut-out) RW 11178 5179 Application 130 only. TODO: FORMAT
??? R? 11179 N/A Application 130 only. Desired room temperature?
??? R? 11180 N/A Application 130 only. Manual temperature?
Gain - max. (room temp. limitation, max.) RW 11181 3182 Application 130 only. TODO: FORMAT
Gain - min. (room temp. limitation, min.) RW 11182 3183 Application 130 only. TODO: FORMAT
Xp (proportional band) RW 11183 6184 TODO: FORMAT
Tn (integration time constant) RW 11184 6185 TODO: FORMAT
M1 run (running time of the motorized control valve) RW 11185 6186 TODO: FORMAT
Nz (neutral zone) RW 11186 6187 TODO: FORMAT
Min. on time (min. activation time gear motor) RW 11188 7189 TODO: FORMAT
??? R? 11189 N/A Application 116 only.
??? R? 11190 N/A Application 116 only.
Daylight (daylight saving time changeover) RW 11197 7198 TODO: FORMAT
ECL address (master / slave address) RW 11198 7199 TODO: FORMAT
??? R? 11200 N/A S1 actual readout in 0.1°C, 192°C = not connected
??? R? 11201 N/A S2 actual readout in 0.1°C, 192°C = not connected
??? R? 11202 N/A S3 actual readout in 0.1°C, 192°C = not connected
??? R? 11203 N/A S4 actual readout in 0.1°C, 192°C = not connected
??? R? 11220 N/A
??? R? 11221 N/A
??? R? 11222 N/A
??? R? 11223 N/A
??? R? 11228 N/A Application 130 only. S2 desired readout
??? R? 11229 N/A S3 desired readout
??? R? 60007 N/A
??? RW 60020 N/A
??? R? 60025 N/A
Backlight (display brightness) RW 60057 8310 TODO: FORMAT
Contrast (display contrast) RW 60058 8311 TODO: FORMAT
Hours RW 64044 1000 Valid range 0...23
Minutes RW 64045 1000 Valid range 0...59
Day RW 64046 1000 Valid range 1...31 depending on month
Month RW 64047 1000 Valid range 1...12, cannot be set if currently set day is greater than number of days in given month
Year RW 64048 1000 Year number since 2000, valid range 1..40
??? R? 65534 N/A
??? R? 65535 N/A